Smart Direct Current Distribution Unit(Smart DCDU)
iPDU-1U10
Functions:
1. Electrical protection: Overload, Short Circuit and OverVoltage
2. DC power distribution
3. Remote Control
4. Local Control
5. Monitoring for each smart CB
6. Electrical parameter threshold setting: DC Voltage, Current,
7. Timer control and setting for each smart CB
8. Disable control
9. Alarm
Technical Specification
|
|
Item |
Parameter |
Working Voltage
|
40~60VDC
|
Power consumption
|
<5W
|
Power input
|
48VDC 250A
Total number of input points: 2 pairs
|
Power output
|
2pairs (48V 63A/48V 125A)
|
Communication interface
|
1 channel RS485 (interface A1, B1)
|
Other interfaces
|
Other interfaces are reserved
|
Communication Protocol
|
Modbus RTU
|
Number of DC on/off switches
|
>=10000 times
|
Voltage measurement accuracy
|
Class 0.5
|
Current measurement accuracy
|
Class 0.5
|
Energy measurement accuracy
|
Class 1
|
Working temperature
|
-40~65℃
|
Working humidity
|
5~95% (no condensation or freezing)
|
Storage temperature |
-40~70℃
|
Atmospheric pressure
|
70kPa~110kPa
|
Total smart CB output
distribution
|
7 CBs with overload and short circuit protection functions including:
1 CB with rated current = 125A
6 CBs with rated current = 63A
Can be expanded to 04 positions with rated current ≥ 63A
Can adjust from 10A to rated current (In) through Modbus protocol
|
Ability to escape lightning
surges (8/20 µs)
|
Differential-mode: 10 kA
Common-mode: 15 kA
|
Safety standards
|
IEC/EN 62368-1
|
Certificate
|
CE LVD
|
Number of poles
|
1 pole
|
Working type
|
Manual and remote control
|
Insulation voltage (Ui)
|
≥ 500V
|
Impulse test voltage (Uimp)
|
4kV
|
Maximum short-circuit breaking capacity (Icu)
|
10kA
|
Service short circuit breaking
capacity (Ics)
|
10kA
|
Mechanical Life
|
10000 times
|
Electric Life
|
10000 times
|
Tripping Characteristic
|
C curve
|
Ability to withdraw/plug(drawout)
|
Yes
|
Impact time (send from power
supply controller to smart CB)
|
3s
|
Instantaneous tripping current
|
11*In( ± 20%)
|
Each smart CB will have a hard
label affixed/printed on the
DCDU
|
Yes
- Similar to the label on the smart DCDU cabinet controller.
- Can setup label information of each smart CB module on the smart
DCDU cabinet controller
|
Manufactured according to
standards
|
Yes, IEC/EN IEC/EN 62368-1
|
Input power connection type
|
+ Tournament style
+ Fits cos up to M6 or larger and DC input wire cross section 35mm2
or larger (including negative and positive power input)
|
Output connection type
|
+ Power out on the front panel
+ Suitable for wires with a cross section of up to 16 mm2 (including 9 Instruction Manual
negative and positive power inputs) (with CB In ≥ 63A)
+ Suitable for wires with a cross section of up to 35 mm2 (including
negative and positive power inputs) (with CB In ≥ 125A)
|
Weight
|
≤ 10 kg (power cable not included)
|
Installation type
|
19 inch rack
|
Height
|
1U
|
Case
|
Powder-coated galvanized steel or equivalent
|
Grounding point
|
There is a grounding position
|
Dimensions
|
440mm(L)*260mm(W)*44.5mm(H)
|
Contact Us
* Name:
* Phone:
* E-mail:
* Interested in:
* Content:
- Solutions
- Products & Support
- Cases
- About us
- Contact
TEL:+86 18621879631
Email:timmy@matismart.com
Mobile phone:+86 15801814653
Address:Room 320, No.83, Huanhu West Road 3, Pudong, Shanghai, China, 201306
Wechat:+86-15801814653
Skype:timmybao2008
Copyright © Shanghai Matis Electric Co.Ltd沪ICP备09024882号-1